Congratrulations! Haibian Power Equipment Co., Ltd. has 12kv & 24kv Gas insulated Switchgear successfully finished STL Membership ASTA test items.33kV ASTA test is under proceeding,welcome a world wide cooperators!

33kV Polymer Housing Metal-oxide Surge Arrester

Application Protection of medium/high voltage AC networks against both, multiple atmospheric and switching overvoltage as well as Very Fast Transients (VFT). Suitable for the protection of transforme

Application

Protection of medium/high voltage AC networks against both, multiple atmospheric and switching overvoltage as well as Very Fast Transients (VFT). Suitable for the protection of transformers, transformers in arc fumace applications, cables, generators, parallel to capacitor banks, and railway vehicles. Can be used mechanically as support insulator or as suspension insulator in case of application as line arrester. For indoor and outdoor installation.

 

Keystone

The metal-oxide surge arrester (MOSA) is the most advanced overvoltage protector in the word. Due to make the varistor of core component mainly adopt MOSA. Compared with the conventional silicone carbide arrester, this prescription of the product improves greatly the Voltage-Current(U-I) characteristic of the metal-oxide varistor and increased through-current capability at over-voltage so as to bring a radical-changes for the characteristic of the MOSA.

Under the circumstance of normal operating voltage, the current through the MOSA just on microampere degree. When suffered from overvoltage, the MOSA's excellent non-linear characteristic will make the current through the MOSA increase to several thousand ampere, While the MOSA will be under the circulating state and release overvoltage energy so as to protecting the power transmission equipments against the damage caused by the overvoltage.

 

Usual service condition

a) Ambient air temperature within the range of -55℃ to+50℃.

b) Altitude not exceeding 2000m.

c) Frequency of the A.C. power supply not less than 48Hz and not exceeding 62Hz.

d) Power frequency voltage applied continuously between the terminals of the arrester not exceeding its continuous operating voltage.

e) Maximum wind speed not exceeding 35m/s.

f) Earthquake intensity not exceeding 7 degrees.

 

Advantage

-Low residual voltage

-Long protection distance

-High energy input capacity

-Stable U-I characteristic even after multiple strokes

-Proof against ageing

-Explosion and shatter-resistant design

-Pollution resistant and UV-stable

-Housing resistant to rough handling

-Maintenance free

-Stable against shock and vibration

-High mechanical resistance

 

Technical Performance

The technical performance of metal-oxide surge arrester is accord with IEC60099-4, IEEE(ANSI)C62.11 and GB11032.

 

Configuration and Anatomy Design of Polymer Housing Metal-oxide Surge Arrester

33kV Polymer Housing Metal-oxide Surge Arrester

Metal-oxide Surge Arrester

33kV Polymer Housing Metal-oxide Surge Arrester

 

5KAGapless arrester electrical parameter

Type

Rated voltage(kV)

MCOV(kV)

Residual voltage(kV)

2000μs square wave impulse current withstand

4/10μ s high current impulse (kV)

 

 

 

Steep current impulse

switching current impulse

8/20μs Lightning current impulse

 

 

HY5W-3

3

2.55

9.5

7.7

9

100

65

HY5W-6

6

5.1

19.5

15.4

18

100

65

HY5W-9

9

7.65

28.5

23.1

27

100

65

HY5W-10

10

8.4

36

30

23

150

65

HY5W-11

11

9.4

40

33

30

150

65

HY5W-12

12

10.2

38

30.8

36

100

65

HY5W-15

15

12.7

47.5

38.5

45

100

65

HY5W-18

18

15.3

57

46.2

54

100

65

HY5W-21

21

17

66.5

53.9

63

100

65

HY5W-24

24

19.2

76

61.6

72

100

65

HY5W-27

27

21.9

85.5

69.3

81

100

65

HY5W-30

30

24.4

95

76.5

90

100

65

HY5W-33

33

26.8

104.5

84.7

99

100

65

HY5W-36

36

29

114

92.4

108

100

65

HY5W-42

42

34.1

132.3

100.1

126

100

65

 

33kV Polymer Housing Metal-oxide Surge Arrester

10KAGapless arrester electrical parameter

Type

Rated voltage(kV)

MCOV(kV)

Residual voltage(kV)

2000μ s square wave impulse current withstand

4/10μ s high current impulse (kV)

 

 

 

Steep current impulse

switching current impulse

8/20μs Lightning current impulse

 

 

HY10W-3

3

2.55

9.5

7.7

9

1

100

HY10W-6

6

5.1

19.5

15.4

18

1

100

HY10W-9

9

7.65

28.5

23.1

27

1

100

HY10W-10

10

8.4

36

30

23

250

100

HY10W-11

11

9.4

40

33

30

250

100

HY10W-12

12

10.2

38

30.8

36

1

100

HY10W-15

15

12.7

47.5

38.5

45

1

100

HY10W-18

18

15.3

57

46.2

54

1

100

HY10W-21

21

17

66.5

53.9

63

1

100

HY10W-24

24

19.2

76

61.6

72

1

100

HY10W-27

27

21.9

85.5

69.3

81

1

100

HY10W-30

30

24.4

95

76.5

90

1

100

HY10W-33

33

26.8

104.5

84.7

99

1

100

HY10W-36

36

29

114

92.4

108

1

100

HY10W-42

42

34.1

132.3

100.1

126

1

100

HY10W-48

48

39

152

126

150

1

100

HY10W-54

54

43

171

139

162

1

100

HY10W-60

60

48

208

160

180

1

100

HY10W-66

66

52.8

230

172

198

1

100

Feedback