HXGN17-12 Box Type Fixed Metal Enclosed Switchgear
PRODUCT DESCRIPTION
HXGN17-12 box type fixed ring network high-voltage switch (referred to as ring main unit) is AC high voltage electrical device with rated voltage of 12KV, rated frequency of 50Hz, mainly for reception, distribution of electricity of three-phase AC ring network, terminal distribution network and industrial equipment, it is also suitable for equipment's substation.
Model and Meaning
The Main Technical Parameters
No. |
Ltem |
Unit |
FN12-12 |
FZN25-12 |
|
1 |
Rated voltage |
kV |
12 |
||
2 |
1min power frequency withstand voltage |
|
To earth and between phase42;Disconnet break48 |
||
3 |
Lightning impulse voltage (peak) |
|
To earth and between phase75;Disconnet break85 |
||
4 |
Rated current |
Hz |
50 |
||
5 |
Main bus' s rated current |
A |
630 |
||
6 |
Load break switch |
Rated current |
|
630 |
|
7 |
Life in rated current |
Time |
No less than 100 |
||
8 |
Capacity of breaking no-load transformer |
kVA |
1250 |
||
9 |
Rated thermal stable current |
kA/S |
20/4;Grounding switch 20/2 |
||
10 |
Rated dynamic current(peak) |
kA |
50 |
||
11 |
Rated short circuit closing current(peak) |
|
50 |
||
12 |
Combined appliance |
Fuse' s rated current |
A |
100 |
|
13 |
Rated transfer current |
|
1500 |
2000 |
|
14 |
Rated short circuit breaking current |
kA |
31.5 |
||
15 |
Equipped fuse models |
|
SOLAJ-12(×RNT口-10) |
||
16 |
Mechanical life |
Time |
2000 |
10000 |
|
17 |
Auxiliary mouth 1min power frequency withstand voltage |
kV |
2 |
||
18 |
Circuit operating mechanism operating voltage |
V |
AC/DC 220;110 |
||
19 |
Protection class |
|
IP2X |
||
20 |
Dimensions (W x D x H) |
mm |
650(850)×900×2000(2200) |
Installing Size
Main Circuit Plan